SLAD4.1000 pages
AS-Interface
DC/DC converter with 4A
SLAD4.100
Data sheet
•
•
•
•
EMC and
Low Volt.
Directive
Input: DC 24V
Output: 30.55V / 4A
AS Interface data decoupling
For highly demanding industrial
applications
Short description
The primary switched mode DIN rail DC/DC converter SLAD4.100 specif®
ically supplies AS Interface systems with energy. The AS-Interface bus
technology allows to connect up to 62 participants to a control and to
supply them with energy with a single two-conductor cable.
When connecting slaves, the yellow AS-Interface cable offers the high
degree of protection IP67 in conjunction with the insulation displacement. The communication signals of the individual network participants
are modulated onto the supply voltage. For this purpose, specific DC/DC
converter units with integrated
data decoupling are required for AS-Interface systems.
Output
Input
Rated voltage
DC 24V
Rated voltage
DC 30.55V +/- 3% ( not adjustable )
Input voltage range
18.0-32.4Vdc Continuous operation
See Fig.2
14.0-18.0Vdc max. 60 seconds or with derating
max. 36.0 Vdc Absolute maximum continuous
input voltage with no damage to the DC/DC
converter.
Rated current
4A
Input / output
separation
SELV IEC / EN 60950-1
Allowed voltage be- max. 60Vdc or 42.4Vac
tween input and earth
(ground)
Allowed input ripple max. 5Vpp, 47Hz-40kHz, the momentary input
voltage
voltage must always be within the specified
limits.
Turn-on voltage
typ. 17.5Vdc Steady-state value
Reverse input polarity Included, unit does not start when input
protection
voltage is reversed
Shut down voltage
typ. 14.0Vdc Steady-state value
typ. 35Vdc Steady-state value
Input current
Max. 1.8A peak at -25°C up to +70°C
Inrush energy
Typ. < 1A2s at -25°C up to +70°C
Start-up delay
typ. 650ms
Rise time
typ. 100ms constant current load 4A
typ. 200ms constant current load 4A with
external 5mF capacitor
Integrated internal
fuse
Double or reinforced insulation,
Max. allowed voltage between any input pin
and ground: 60Vdc or 42.4Vac
Current limitation
> 4.4A
Overload behaviour
Continous current, see Fig. 3
Short-circuit current
min. 5A , max. 9A
Load regulation
< 250mV Static value, 0A
4A
0A
Line regulation
< 5mV Input variations between 18 to 32.4Vdc
Ripple
< 50mVpp ( 500kHz bandwith, 50 Ohm measurement, ohmic load)
Noise (spikes)
< 100mVpp ( 20Hz to 20MHz bandwith, 50
Ohm measurement, ohmic load
Over-voltage
protection
Max. 36V
Operating indicator
Green LED (extinguishes at overload)
typ. 5.6A at 24Vdc input and output 30.55V, 4A
Inrush current
PELV IEC 60364-4-41, EN 60204-1, IEC 62103
T10A HBC ( not accessible)
Output is protected against short-circuit, open circuit and overload.
Use AS-Interface DC/DC converters only together with AS-Interface
lines.
External capacitors on the input voltage bus are allowed without any
limitations.
Order information
Order number
slad4e100 / 071026
Description
SLAD4.100
SLZ10
ZM1.Wall
ZM11.SIDE
AS-Interface DC/DC converter
DIN-Rail bracket for S7-300 Simatic-Rail
Wall mounting bracket
Side mounting bracket
1/4