ML50.1090 pages
ML50.100, ML50.109
24V, 2.1A, SINGLE PHASE INPUT
MiniLine
POWER SUPPLY
■
■
■
■
■
■
■
■
■
■
AC 100-240V Wide Range Input
NEC Class 2 Compliant
Adjustable Output Voltage
Efficiency up to 89%
Compact Design, Width only 45mm
Full Output Power Between -10°C and +60°C
DC-OK Signal Included
Large International Approval Package
DIN-Rail Bracket for Wall or Panel Mount Included
3 Year Warranty
1. GENERAL DESCRIPTION
2. SHORT-FORM DATA
A compact size, light weight, simple mounting on
the DIN-rail and the quick connect spring-clamp
terminals are what makes the MiniLine power
supplies so easy to use and installs in seconds.
Output voltage
Adjustment range
Output current
DC 24V
24-28V
2.1–1.8A
A rugged electrical and mechanical design as well as
a high immunity against electrical disturbances on
the mains provides reliable output power. This offers
superior protection for equipment which is
connected to the public mains network or is exposed
to a critical industrial environment.
Output power
50W
Output ripple
Input voltage
Mains frequency
AC Input current
Power factor
AC Inrush current
< 50mVpp
AC 100-240V
50-60Hz
typ. 0.77 / 0.44A
typ. 0.56 / 0.52
17 / 35A
DC Input
Efficiency
Losses
Temperature range
Derating
Hold-up time
Dimensions
85-375Vdc
typ. 88.4 / 89.0%
typ. 6.6 / 6.2W
-10°C to +70°C
1.3W/°C
typ. 35 / 190ms
45x75x91mm
The MiniLine series offers output voltages from 5 to
56Vdc and a power rating of up to 100W. A DC-OK
signal allows remote diagnostics.
The supplementary MiniLine decoupling diode
module MLY02.100 allows building of redundant
systems or to protect against back-feed voltages.
Screw
terminals
24V MiniLine
Related products
ML30.100
Less
ML50.100
power
For other output voltages or
output power see catalog
ML50.111
Conformal
ML50.109
coating
Parallel use
ML50.101
option
More
ML100.100
power
380-480V
ML100.200
input
3. ORDER NUMBERS
Power Supply
Accessory
ML50.100
ML50.109
MLY02.100
24-28V
20Hz to 20MHz
Wide Range Input
±6%
at 120 / 230Vac
at 120 / 230Vac
typ. peak value
at 120 / 230Vac
40°C and cold start
at 120 / 230Vac
at 120 / 230Vac
operational
+60 to +70°C
at 120 / 230Vac
WxHxD
4. MARKINGS
Standard unit
Conformal coated unit
Decoupling /
Redundancy module
IND. CONT. EQ.
UL 60950-1
UL 508
NEC Class 2
&
Medical
approval
GL
Marine
Mar. 2007 / Rev. 1.0 DS-ML50.100-EN
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0
Class I Div 2
Germany
EMC, LVD
1/20
"