SL20.1120 pages
SL20 with 36...43V
Data sheet
SL20.112
•
•
•
•
CB
scheme
IEC60950
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
Input: AC 115/230V auto select
Output: 36...43V / 480W
92% efficiency
Ideal for parallel operation
UL60950 E137006
CUL/CSA-C22.2
No 60950
Type approval
acc. to:
• IEC / EN60950
• EN50178
Overvolt. cat. III
• EN60204
EMC and
Low Volt.
Directive
Datasheet
Input
Input voltage
Rated tolerances
• Continuous
operation
• Short-term (30s)
at 36V/13A
Input current In
Output
AC 100-120V/220-240V,
47-63Hz, auto select
Output voltage
DC 36...43V, adjustable by (covered) front
panel potentiometer; preset: 36V ±0.5%
Adjustment range guaranteed
AC 85...132V resp. AC 184...264V
Output noise
suppression
Radiated EMI values below EN50081-1, even
when using long, unscreened output cables.
Ambient temperature
range Tamb
Operation: 0°C...+70°C (> 60°C: Derating)
Storage: -25°C...+85°C
AC 85...140V resp. AC 175...280V
<10A (115V range)
<5A (230V range)
Inrush current limiting with active bypass of the limiting resistor (NTC).
Rated continuous loading with convection cooling:
• Tamb=0°C - 60°C
36V/13.3A resp. 43V/11.2A
short-term (<30s)
36V/16.6A resp. 42V/14A
Inrush current Ipk
<18A @ AC 264V (Tamb = +25°C, cold start)
<37A @ AC 264V (Tamb = +50°C, cold start)
Derating
12W/K
Voltage regulation
better than 2% over all
Fuse loading I²t
<5A2s (Tamb = +25°C, cold start)
<8A2s (Tamb = +50°C, cold start)
Ripple
• Output charact. S
• Output charact. P
(incl. spikes (20 MHz bandw.), 50Ω measurem.
<30mVPP (<0.09%)
<80mVPP (In: AC 230V, Out: 36V/13A)
<100mVPP (In: AC 184V, Out: 42V/13A)
To be fused with a 16A, B-type 'circuit-breaker' switch based on the usual thermomagnetic overload sensing principle (used anyway to fuse the
input lines).
EN 61000-3-2 (harmonic current emissions [PFC]) is fulfilled
Transient
handling
Transient resistance acc. to VDE 0160 / W2
(750V / 1.3ms), for all load conditions.
Hold-up time
27ms at 36V/13A, AC 230Vin
35ms at 36V/13A, AC 120Vin
15ms at 36V/13A, AC 100Vin
(S/P: Single/Parallel Mode)
Over-voltage protection
(at Tamb = 60-70°C)
At 49V ±10%: switch to hiccup mode
Front panel indicators:
• Green LED on, when Vout = Vout adjusted
• Red LED on, when Vout < Vout adjusted
Parallel operation
Yes, up to ten SL20
To achieve current sharing the output V/I characteristic can be altered to
be 'softer' (36.6V at 0A, 35.2V at 13.3A). This is done by repositioning an
external bridge connection (without opening the unit).
Power Back Immunity
max. 48V
Construction / Mechanics
Housing dimensions and Weight
220mm x 124mm x 102mm (+ DIN rail)
• WxHxD
above/below 70mm recommended
• Free space for
left/right 25mm recommended
ventilation
2.5kg
• Weight
Design advantages:
• All connection blocks are easy to reach as mounted on the front
panel.
• PVC insulated cable can be used for all connections, as the connection
blocks are mounted in the cooler area on the underside of the unit.
Order information
Order number
SL20.112
SLZ02
sl20e112 / 040114
Description
(wall mounting set; contains 2 pcs.)
1/2