FLEX6024A 0 pages
All specifications are subject to change without notice
RoHS
Input: single-phase: 115 – 230 Vac
Output: 24 Vdc 50°C
Efficiency up to 88%
Strong overload without switch-off
Flexible Power continuity : from 36 to 72 W
DIN Rail Mountable
Extremely small size
3 Year warranty
Features
Input Data
Nominal Input Voltage (2 x Vac)
115 – 230 Vac
Input Voltage range (Vac)
90 – 264
Inrush Current (Vn and In Load) I2t
„T 7 A „T 5 msec.
Frequency
47 – 63 Hz „b6%
Input Current (115 – 230 Vac)
1 – 0.7 A
Internal Fuse
T 4 A
External Fuse (recommended)
6 A (MCB curve B)
Output Data
Output Voltage (Vn) Factory Setting „b3%
24 Vdc
Adjustment range (Vadj)
22 – 27 Vdc
Start up with Strong Load (capacitive load)
„T 50.000ƒÝF
Turn-On delay after applying mains voltage
1.5 sec. (max)
Continuous Current at 24 V < 40°C (In)
2 A (115) 3 A (230)
Continuous Current at 24 V < 50°C (In)
1.5 A (115) 2.5 A (230)
Power Boost Current at 24 Vdc 50°C(In)
3.5 A „d 3 min.
Current max. Overload ƒ° 4Vdc (permanent)
Imax=In50°Cx(1.8 - 2.2)
Max current Short Circuit (Icc)
7 A
Hold-up Time ( min. Vac) 24Vdc 5A
Typ. 20 msec
Residual Ripple
„T 80 mVpp
Efficiency
„d 88 %
Over temperature Protection
Yes. Shut-down output and automatic restart.
Short-circuit protection
Yes, Continuous Mode
Dissipation power load max (W)
6
Over Load protection
Yes, Continuous Mode
Over Voltage Output protection
Yes (typ. 35 Vdc)
Parallel connection
Yes
Climatic Data
Ambient Temperature operation
-25 up to +70 °C
(>50°derating 2.5% °C)
Ambient Temperature Storage
-40 up to +85 °C
Humidity at 25 °C, no condensation
95 % to 25 °C
General Data
Isolation Voltage (In / Out)
3000 Vac
Isolation Voltage (In / PE)
1605 Vac
Isolation Voltage (Out / PE)
500 Vac
Protection Class (EN/IEC 60529)
IP 20
Reliability: MTBF IEC 61709
> 500.000 h
Pollution Degree Environment
2
Connection Terminal Blocks Screw Type
2,5 mm (24 – 14 AWG)
Protection class
I with PE connected
Dimension (w-h-d)
50x120x50 mm
Weight
0.3 kg approx.
Norms and certifications
The CE mark in According to EMC 2004/108/EC and Low voltage directive 2006/95/EC.
Electrical Safety
In compliance to UL508.
According to IEC/EN 60950 (VDE 0805) e EN 50178 (VDE 0160) for assembling device. The unit must be installed according to IEC/EN 60950.Input / Output separation: SELV EN60950-1 and PELV EN 60204-1. Double or reinforced insulation.
EMC Immunity
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN61000-6-2
EMC Emission:
EN61000-6-4, EN61000-3-2
Standards Conformity
EN 60204-1 Safety of Electrical Equipment Machines
Output derating CurveContinuous Load 020406080100120140160-10010203040506070°C%
FLEX6024A