D Series Room version0 pages
Galltec Mess- und Regeltechnik GmbHt
D-71145 Bondorf . Germany t
Tel. +49 (0)7457-9453-0 . Fax +49 (0)7457-3758 t
E-Mail: sensoren@galltec.de . Internet:www.galltec-mela.det
MELA Sensortechnik GmbH
D-07987 Mohlsdorf-Teichwolframsdorf . Germany
Tel. +49(0)3661-62704-0 . Fax +49(0)3661-62704-20
E-mail:mela@melasensor.de . Internet: www.galltec-mela.de
D Series
Sensors for
Humidity and Temperature Measurement
With calibrated dModul
Type DI
Room version
Optional display
•t dynamic MELA® humidity sensing element
• tcalibrated dModul for
t humidity and temperature measurement
•t with integrated measuring chamber
•t easy to install
•t operating temperatures up to 60°C
Technical data
Humidity
measuring element
capacitive MELA FE09
output range
0...100 %RH
measuring uncertainty
40...60 %RH
(at 23°C / UB=24 V DC )
10...40 %RH or 60...90 %RH
(at 23°C / UB=24 V DC )
±2.5 %RH
±3 %RH
influence of temperature (ref. to 23°C)
typ. ±0.05 %RH/K
Temperature
measuring element
Pt1000
output ranges
0...+50°C
-30...+70°C
0...+100°C
further ranges on request
measuring uncertainty
(UB=24 V DC )
sensors with active temperature signal
voltage output 10°C...40°C
current output 10°C...40°C
±0.25 K
±0.4 K
influence of temperature <10°C or >40°C
typ. ±0.01 K/K
The core part of the D Series is the digital calibrated dModul,
which processes the measurement values of relative humidity
and temperature individually. The values are compared to the
calibration values stored in the dModul and communicated
digitally to the transmitter electronics, where they are processed
to standardised current and voltage signals.
The integrated measuring chamber of the room version is separated from the electronics. Thus, a good air circulation around
the sensing elements is provided.
The housing of the room version has a simple and robust closing mechanism. After mounting the base part, the top which
contains the transmitter electronics, can be easily clipped into
place and pressed shut without any tool.
Electrical data
outputs
0...1 V
0...10 V
4...20 mA
passive temperature outputs on request
voltage supply
see type survey
consumption of electronics
(voltage output)
min. load resistance
(voltage output)
Load at current output
Ω 1200
Ω 1200
load RL
(current output)
1000
1000
800
800
electromagnetic
compatibility
600
600
400
400
typ. 7 mA
≥10 kΩ
RL(Ω)=
voltage supply - 10 V ±50 Ω
0,02 A
ref. EN 61326-1
and EN 61326-2-3
Options
display
200
200
10
10
15
15
www.galltec-mela.de
20
20
25
25
30
V30 VV DC
DC DC
2 lines
3 digits + 1 decimal place
display approx. 21 x 40 mm²
digit height approx. 8