AS-Interface
power on three phases
Data sheet
SLA8.300
•
•
•
•
•
•
•
Input: 3 AC 400-500V
No neutral wire required
Output: 30.5V / 8A
AS Interface data decoupling
Infrared (IR) addressing mode
Overload protection by FUSE Mode
For highly demanding industrial
applications
Appr.No. 41701
EMC and
Low Volt.
Directive
Short description
Data and energy:
The primary switched mode DIN rail power supply SLA8.300 specifically
supplies AS Interface® systems with energy. The AS-Interface bus
technology allows to connect up to 62 participants to a control and to
supply them with energy with a single two-conductor cable. When
connecting slaves, the yellow AS-Interface cable offers the high degree
of protection IP67 in conjunction with the insulation displacement. The
communication signals of the individual network participants are
modulated onto the supply voltage. For this purpose, specific power
supply units with integrated data decoupling are required for ASInterface systems.
Fast addressing of slaves:
The "IR addressing mode" selectable via jumper interrupts the data com-
Input
munication on the yellow AS-Interface cable. Participants with an infrared interface can then quickly be assigned a new ID address by means of
an infrared programming unit without the need to disconnect them
from the AS-Interface cable. Afterwards, the "Communication Mode"
can be selected again to restart the data communication.
Safe operation by FUSE Mode:
The device features a FUSE Mode, which permanently switches off the
output in the event of failure and the unit at overload, short-circuit or
overtemperature and thus protects the relatively thin AS-Interface line
and the attached components. Triggering of the FUSE Mode is indicated
by a flashing LED. System restart requires the intentional activation of a
reset button on the front side of the unit. Thus, an accidental restart is
prevented and the slaves are protected against damage.
Output
Rated voltage
3 AC 400-500V
Rated voltage
DC 30.5V ±3% (not adjustable)
Rated current
3 x 0.8A/0.7A at AC 400V/500V
Rated current
8A
Frequency
47...63Hz (alternatively also DC possible)
Isoltation
Safe low voltage
Voltage range
3 AC 340...576V, DC 450...820V
Current limitation
> 8.4A
Overload behaviour
FUSE Mode (continuous current for 2...5s, afterwards permanent switch-off)
2-phase operation is specified and permissible. Connection to 3 phases
is recommended due to reduced component stress. Internally fused on
each phase. External fusing is only necessary as required for input line
protection.
PELV (IEC364-4-41)
SELV (IEC60950)
>0.52
Integrated internal
fuses
3xT2A5 HBC (not accessible)
Short-circuit current
>14A, <20A (max. 5s)
Load regulation
Power factor
stat. 250mV (no load / full load)
line regulation
stat. 100mV (3 AC 340...550V)
limited by NTC resistor
Tamb = +60°C, cold start
(line impedence acc. EN 61000-3-3)
Ripple
50 mVPP (500kHz bandw., 50Ω measurem.,
ohmic load)
Noise (Spikes)
Peak current Ipk
3 AC 400V
<50A
3 AC 500V
<60A
DC 820V
<70A
100mVPP (20MHz bandw., 50Ω measurem.,
ohmic load)
Overvoltage protection limited to max. 50V
I2 t
<1.5A2s
<2.5A2s
<3.5A2s
Operating indicator
Inrush current
EN 61000-3-2 (harmonic current emissions) is fulfilled
Hold-up time
>18ms (3-phase operation at AC 340V and
rated load); also see diagram
Green LED (extinguishes at overload)
Output is protected against short-circuit, open circuit and overload.
Use AS-Interface power supplies only together with AS-Interface lines!
Order information
Order number
sla8e100 / 040225
Description
SLA8.300
SLZ02
AS-Interface power supply unit
Wall mounting set (two pcs. per package)
1/4