C20/2H - AC Current Probes0 pages
AC Current Probes
Model C20/2H
Current | 20 A AC | 200 A AC |
Ou put | 100 mV/A | 10 mV/A |
■ Electrical specifications
Current range :
0.1...24AAC
0.5...240AAC
Output signal:
100 mV AC/A AC (2.4 V at 24 A)
10 mV AC/A AC (2.4 V at 240 A)
Accuracy and phase shift (1):
Range | 20 A | 200 A | |||
Primary current | 0.1...20 A | 0.5...10 A | 10...40 A | 40 A ...100 A | 100...240 A |
% Accuracy of output signal | < 1% + 50 mV | < 3% + 5mV | <, 2.5% + 5 mV | < 2% + 5 mV | < 1% + 5mV |
Phase shift | not specified | not specified | <5° | <3° | <2.5° |
Bandwidth :
40 H2...10 kHz
Crest factor:
3 for a current of 200 A rms
Max. currents:
200 A continuous for a frequency
< 1 kHz (Limitation proportional to
inverse frequency beyond)
Load impedance:
> 1 MQ
Working voltage:
600 V rms
Common mode voltage :
600 V for category III and pollution level 2
Influence of adjacent conductor:
<15mA/A at 50 Hz
Influence of conductor position in
the jaws:
< 0.5% of output signal 50/60 Hz
Influence of frequency (2):
■ 20 A range :
< 5% of output signal 40 HZ...1 kHz
< 15% of output signal 1 kHz...10 kHz
■ 200 A range :
< 3% of output signal 40 Hz...1kHz
< 12% of output signal 1 kHz...10 kHz
Influence of crest factor:
< 3% of output signal for a crest factor of
3 and current of 200 A rms
■ Mechanical specifications
Operating temperature:
-10°tO+55°C
Storage temperature:
-40° to +70°C
Influence of temperature:
< 0,15% of output signal per 10 K
Working humidity :
From 0 to 85% of RH with linear decrease
beyond 35°C
Influence of humidity :
< 0.2% of output signal 10% to 85% of RH
Operating altitude:
0 to 2000 m
Max. jaws opening:
20 mm
Max. conductor size:
Cable : 0 max 20 mm
Busbar: 1 busbar of 20 x 5 mm
Casing protection level:
IP 40(IEC 529)
Drop test:
1 m(IEC 68-2-32)
Shock resistance:
100 g (I EC 68-2-27)
Vibration resistance:
10/55/10 Hz, 0.15 mm (IEC 68-2-6)
Self-extinguishing ability :
Case : UL 94 V2
Jaws : UL 94 V0
Dimensions :
135 x 51 x 30 mm
Weight:
180 g
Colours:
Dark grey case with red jaws
Ouput:
Insulated 1.5 m lead with safely (4 mm)
banana plugs.
■ Safety specifications
Electrical :
Double insulated or reinforced insulation
between primary, secondary and outer
case according to IEC 1010-1 & IEC
1010-2-032
- 600 V category III, pollution level 2
- 300 V category IV, pollution level 2
Electromagnetic compatibility
(EMC Mark):
EN 50081-1 : Class B
EN 50082-2 :
-Electrostatic discharge : IEC 1000-4-2
-Radiated field : IEC 1000-4-3
- Fast transients : IEC 1000-4-4
- Magnetic field to 50 Hz : IEC 1000-4-8
(1) Reference conditions : 23 'C * 3"K, 20 to 70 % RH, sinusoidal signal frequency 4& Hz 1o 65 Hz, external magnetic fields 40 A/m. no DC componenls. no external current carrying
conductor, test sample centered, >1 M£i load.
(2) Out of reference field
"