400KH/400KHK0 pages
400KH/400KHK
©HINODE
Founded if 19S&
HINODE ELECTRIC CO.,LTD.
1-18-9 Hokima. Adachi-ku, Tokyo 121-0064* JAPAN
URL:hnp;//www.hinodedenki.co.|p
FEATURES
•The full length is 26 mm (KHK), which is convenient to arrange on the
board.
• Being extremely compact, it is compliant to 400V-50A class.
•Contribute to miniaturizing the equipment.
•Most suitable for small inverters, servos, UPSs, power supplies, etc.
•Two types are available lor choice according to the installation method.
RATING
• Rating 5-30A
Rated voltage and breaking capacity: 400V AC - 10kA, 400V DC (L/R = 5ms)-10kA
Minimum breaking current: 400V AC/DC - 4 times the rated amperage
Maximum arc voltage : 800V
• Rating 35-60A
Rated voltage and breaking capacity: 400V AC-l0kA, 400V DC (L/R = 2ms)-10kA
Minimum breaking current: 400V AC - 5.3 times the rated amperage
400V DC - 20 times the rated amperage
360V DC - 8 times the rated amperage
Maximum arc voltage : 800V
4*
400KHK
UL standard approved ratin
When applying the standard to UL standard approved items, use the fuse in the
following rating.
• Rating 5-30A
Rated voltage and breaking capacity: Same as the standard rating
• Rating 35-60A
Rated voltage and breaking capacity: 400V AC-tOkA
360V DC (UR = 2msH0kA
CAUTIONI
• Read "FOR SAFE USE" and "PROTECT FUSE USER'S GUIDE" at the back of this
catalog before use.
•A small fuse may generate a relatively large amount of heat, so a fuse with
sufficient capacity is recommended for a long, continuous use.
• Fusing indication function is not provided.
Specifications
Type
400KH-5UL
400KHK05UL
400KH-10UL
400KHK10UL
400KH-15UL
400KHK15UL
400KH-20UL
400KHK20UL
. Rated
Amperage
(A)
400KH-25UL
400KHK25UL
400KH-30UL
400KHK30UL
4QOKH-35UL
400KHK35UL
40OKH-40UL
400KHK40UL
400KH-50UL
400KHK50UL
400KH-60UL
400KHK60UL
Fusing I't
(A'S)
10
15
20
25
30
35
40
50
60
12
25
43
67
99
177
264
314
Shutdown I't
(A'S)
MAC400V1WA
30
70
130
280
420
700
1000
1600
2100
2300
Power Loss
(W)
0.5
0.5
1.0
1.1
1.6
1.7
2.3
2.9
2.8
2.9
2.8
3.9
2.8
5.2
3.3
5.2
4.5
6.9
5.4
7.1
Weight
KH=
10.5
KHK=
8.5
Fig
KH=
Fig 1
KHK'
Fig 2
Ta=25'C
Standard
Approved
TO
TO
Dimensions
Fig 1
400KH
46.5
26
11-S
Fig 2
400KHK
2$
105
05
1=0.6
Fusing Characteristics
Current-Limiting Characteristics
10 15 20 25 3035405060
10*
Electric Current (A) rms
103
10* 103
Prospective Current (A) rms
8
Catalog No. c!10- 05
"