Type 1367 High-Pressure Instrument Supply System with Overpressure Protection0 pages
Bulletin 71.1:1367
nnnnFebruary 2013
nnnnType 1367 High-Pressure Instrument Supply
nnnnSystem with Overpressure Protection
nnnn•3
nnnnPC Ml FlJO
nnnnFigure 1. Type 1367 High-Pressure Instrument Supply System
nnnnIntroduction
nnnnThe Type 1367 high-pressure instrument supply
nnnnsystem takes a pressure of up to 2000 psig /138 bar
nnnnand reduces it to a controlled pressure to be used
nnnnfor supplying a pneumatic instrument. This system
nnnnconsists of the following filters, regulators, and
nnnnrelief valves:
nnnn• A Type 252 extended body filter with drain valve.
nnnn• A first-stage Type 1301F regulator with mounting
nnnnbracket for an actuator yoke or casing.
nnnn• A Type H120 relief valve mounted in the side
nnnnoutlet of the Type 1301F regulator.
nnnn• A second-stage Type 67CF filter-style regulator,
nnnnmounted on the Type 1301F regulator.
nnnn• A Type H800 orH120 relief valve nipple-mounted
nnnnin the outlet of the Type 67CF regulator.
nnnnFeatures
nnnn• Regulation and Overpressure Protection in
nnnnOne Complete Package — This system provides
nnnntwo-stage pressure reduction with a non-adjustable
nnnnrelief valve matched to each regulator.
nnnn• Installation Flexibility — The Type 1367 system
nnnncan be ordered for mounting on either the yoke or
nnnncasing of an actuator.
nnnn• NACE Capabilities — For sour gas applications,
nnnnthe Type 1367 system is available in materials
nnnnthat comply with the recommendations of NACE
nnnnInternational standard MR0175.
nnnn• Capability for Continuous Moisture Removal —
nnnnThe drain valves can be removed from both the
nnnnType 252 filter and the Type 67CF filter-style
nnnnregulator, and tubing installed to provide
nnnncontinuous drains.
nnnnwww.fisherregulators.com
nnnnEMERSON
nnnnProcess Management
"