TA-2008/TA-2016MB Digital Modbus0 pages
MIL-RAM TECHNOLOGY
Since 1990
Gas Detection Controller
Digital Modbus RTU smarter Transmitter Network
TA-2016MB-WM Controller Features
♦ Use with any Mil-Ram Model TA-2100MB smarter Transmitter.
Toxic/LEL/VOC/Oxygen: hundreds of different gases and vapors.
♦ 16-Channel system utilizing RS-485 Modbus RTU Network.
♦ Multi-drop Network eliminates separate wiring to each Transmitter.
♦ Four relays (SPDT), 10 Amp. common to all channels. Select latching
or non-latching function. Low, Mid, High and Fault relays. LED alarm
indicators. Audible buzzer alarm. External alarm stations optional.
♦ Optional: Remote Relay Modules, Modbus enabled, can be installed
at any point on RS-485 network. Up to 16 modules per network.
Up to 16 different zones. Conveniently install relays at point of use.
Eliminates long wiring runs between relays and field installed alarms.
♦ Optional: Remote Analog Output Module. Provides discrete analog
4-20mA output (16 bit resolution) per channel.
♦ Optional: Remote Digital Output Module. Provides RS-485 Modbus
RTU interface to Centralized System (e.g. PLC)
♦ Optional: Analog Input Module to connect standard 4-20mA
Transmitters where traditional analog installation is preferred.
♦ Backlit 16 characters x 2 lines LCD display. Auto-scrolls to provide
channel data and fault conditions. Indicates alarm status.
♦ Simple front panel, push button channel setup. Auto-Configuration
wizard provides rapid channel setup without special knowledge.
♦ Nema 4x weather-proof polycarbonate enclosure (XP available)
♦ Continuous Diagnostics. Wireless Options (consult factory).
Gases & Instrumentation
2010 Golden Gas Award
Digital Modbus
16-Channel Control System
(8 Channel Model Available)
Model TA-2016MB-WM
Auto-Configuration
110 VAC or 24 VDC
16 Channel System
Modbus RTU Network
-up to 16 Gas Detectors
-up to 16 Relay Modules
-up to 16 Alarm Zones
RS-485 Modbus RTU Network
Relay Module
(Analog Input Module available for
connecting traditional 4-20mA Transmitters)
Sensors patented by Mil-Ram
♦ no false alarms Mil-Ram electrochemical sensor technology
♦ No zero drift with changes in temperature/humidity/pressure
♦ No LEL, methane, hydrocarbons, CO, C02, VOCs gas interference
♦ Do not saturate with occasional exposure to high gas levels
♦ Do not go to sleep after long periods in gas-free air
♦ Chemically selective based on unique electrolyte chemistry
♦ Long life: >3 years typical under normal operating conditions
Gas
Detectors
Model TA-2100MB smarter Transmitters
(LEL, Toxic, VOC, Infrared, MOS, more)
MIL-RAM TECHNOLOGY, INC.
REGISTERED TO ISO 9001:2008
FILE NUMBER 10000574 QM08
Patented Technology
no false alarms
Gas Detection Systems
ISO 9001:2008 Registered
Tel: 510-656-2001 • Toll Free: 1-888-4MILRAM (1-888-464-5726)