AA-AT2060 pages
AMF + ATS
AA-AT206
(AA) AMF (Auto Mains Failure) + ATS (Auto Transfer Switch)
From …17 to 44kVA 400Vac 3ph+N
From ….9 to 23kVA 230Vac 1ph
AT 206
This series panels offer the complete manual and automatic
management for generator and electricity network.
All electricity network’s parameters are registered and, in case
of anomaly, the controller will immediately start the generator.
When the voltage is within the programmed limits, genset contactor is immediately closed on load.
During the running period, the engine and the alternator are
monitoring. Any anomaly is showed on the display and,shut
down the engine. At the return of steady electricity network the
controller will open the genset contactor and transfer the load
to the network side. The generator will be stopped after the
cooling time (programmable).
Benefits
Standard Composition
Perfect: Price / Performance ratio
Perfect: Powerful + Technology & Italian Design
Perfect: Easy installation (Big space in Small dimensions)
>t1-metal case 15/10 thick painted by epoxy powder
RAL7042
>1-plastic cover realized by injection pressing, type PPVO, fire
fighting and resistant to atmospheric agents
>3-Protection fuses for auxiliary
>1-Alarm Buzzer
>1-Emergency button
>2-Interlocked power contactors for power changeover
>1-Automatic battery charge - 800mA
>1-Amperometric transformer
>1 TE806 Controller
>tUser friendly
>tExclusive design, with care of every detail
>tMaterials of great quality and resistent
>tElectronic board simple and reliable
>tBig space for an easy connection of the power cables and
engine cables
>tThe only one with the clever automatic management of the
air starter, to ensure the starting of the petrol engines in
every environmental condition
>tSimple and functional battery charger, for a battery always
efficient
>tProgrammable automatic test
>tDisplay to visualize the electrical measures and alarms
>tLeds for the signalation of the functioning state and the
position of the buttons
>tGenerator overload protection
>tRS232 for fast programming by key (1571824) you can
download different set-up
6
Technical data
>tWorking temperature -20 +50°C
>tStocking temperature -30+80°C
>tSupply range 9-17Vdc
>tFrequency range 45 ÷ 65Hz
>t Measures accuracy +/- 5% +/- 1 digit
>t Ambient protection IP20
>tBuilt in conformity to EN60439-1
255CT-AA-AT206