100kVA, 10/12* kV Automatic Resonating Inductor for use with MIDAS System
The capacitive load range of the MIDAS system can
be increased by using this Compensating Reactor
(resonating inductor).
TECHNICAL SPECIFICATIONS
Max. Operating Voltage
Frequency
Maximum Output Current
The 5289 provide an automatic tuneable 15kV,
100kVA inductor coil. It comes into use mainly for
power generator on-site testing. Also a separate
parallel booster supply for the standard MIDAS system
is integrated.
Maximum Output Power
Inductance range
9
Load tuning range
FUNCTION
PD Level @ Max. Output
Duty cycle at full load
The variable inductor is connected in parallel with the
capacitive test object Cx.
This configuration
constitutes a parallel resonant circuit. By adjusting the
inductor Lk the resonant point can be balanced.
Dimensions WxDxH
Weight
Operating Temperature
Storage Temperature
Relative Humidity
In
this
resonant configuration
the
inductor
compensates the reactive power required by the
capacitor and only a smaller portion of real power
(ohmic losses) is taken from the main supply. This
arrangement enables measurement of capacitances
bigger than 1F at 15kV.
15kV rms (50Hz / 60Hz)
50 / 60Hz
7.35A
@50Hz
6.11A @60Hz
100kVA
6.5H .. 162H
22.5 @20°C
0 .. 1.56uF
@50Hz *
0 .. 1.08uF @60Hz *
<500pC
50% at rated output power
over a 16h period. Max.
ON time: 15minutes.
55 x 71 x 108 cm
(22 x 28 x 43")
376 kg (825 lbs)
-10 .. 50°C
-20 .. 70°C
5 .. 95 % r.h.
* use additional base load capacitor if load < 250nF
SCOPE OF SUPPLY
5289 resonating inductor
Base load capacitor 400nF
Connection cable set MIDAS (3m)
Connection cable base load capacitor (20m)
OFFICES:
Europe
Haefely Test AG
Birsstrasse 300
4052 Basel
Switzerland
+ 41 61 373 4111
+ 41 61 373 4912
sales@haefely.com
China
Haefely Test AG Representative Beijing Office
8-1-602, Fortune Street
No. 67, Chaoyang Road, Chaoyang District
Beijing, China 100025
+ 86 10 8578 8099
+ 86 10 8578 9908
sales@haefely.com.cn
North America
Hipotronics, Inc.
1650 Route 22 N
Brewster, NY 10509
United States
+ 1 845 279 3644
+ 1 845 279 2467
sales@hipotronics.com
HAEFELY HIPOTRONICS has a policy of continuous product improvement. Therefore we reserve the right to change design and specification without notice.